Windmill Cables
EPR/HFXLEVA LSOH 0.6/1kV Torsion Resistant Power Cable

  Windmill Cables

LiHCH Multicore Halogen-free Data Cable

LiHCH Multicore Halogen-free Data Cable

Application

These screened, halogen-free cables are designed for special purpose of data transmission in wind turbines, suitable for indoor and outdoor installation.

Standards

VDE 0812

Construction

Conductor: Stranded bare copper.
Insulation: Halogen free compound.
Screen: Tinned copper wire braid.
Sheath: Halogen free compound.

Technical Data

Rated Voltage Uo/U (Um)

250V

Operating Temperatures

flexing: -5℃~+70℃; fixed: -40℃~+70℃

Minimum Bending Radius

flexing: 10×OD; fixed: 7.5×OD

Flame Retardant

DIN VDE 0482 part 265-2-1/EN 50265-2-1/IEC 60332-1

Halogen Free

VDE 0482 part 267/DIN EN 50267-2-1/IEC 60754

Gases Corrosively

VDE 0482 part 267/DIN EN 50267-2-2/IEC 60754

Oil Resistant

Yes

Dimensions and Weight

Construction

Nominal Overall Diameter

Nominal Weight

No. of cores×mm²

mm

kg/km

2×0.14

4.1

22

3×0.14

4.3

25

4×0.14

4.5

29

6×0.14

5.1

35

7×0.14

5.1

38

8×0.14

6.0

41

12×0.14

6.5

78

16×0.14

7.2

90

25×0.14

8.7

149

2×0.25

4.7

25

3×0.25

4.9

30

4×0.25

5.2

35

6×0.25

6.2

49

7×0.25

6.2

52

8×0.25

7.3

58

10×0.25

7.7

81

25×0.25

10.9

172

2×0.34

5.1

30

3×0.34

5.3

35

4×0.34

5.9

42

5×0.34

6.4

53

7×0.34

7.0

73

8×0.34

8.0

84

10×0.34

8.5

101

16×0.34

9.6

160

25×0.34

12.1

259

2×0.5

5.8

38

3×0.5

6.1

47

4×0.5

6.5

67

5×0.5

7.2

76

6×0.5

7.8

84

7×0.5

7.8

91

8×0.5

8.9

131

10×0.5

9.5

135

12×0.5

9.8

177

18×0.5

11.7

239

25×0.5

13.9

352

2×0.75

6.2

45

3×0.75

6.5

69

4×0.75

7.2

80

5×0.75

7.8

99

7×0.75

8.3

120

12G0.75

10.7

168

18G0.75

12.4

237

2×1

6.5

72

3×1

7.0

90

4×1

7.5

109

7×1

8.8

171

10×1

11.2

184

12G1

11.3

205

16×1

12.5

250

19G1

13.1

291

2×1.5

7.7

90

3×1.5

8.1

115

5×1.5

9.5

176

12G1.5

13.0

271

18G1.5

15.5

400

15G2.5

19.8

587